KABUTO TECHNOLOGY
KABUTO AI · Solid-state transformer · 800 VDC

Power Block 2.0

800 VDC. Built for what's next.

KABUTO AI Power Block 2.0

Product renders, not photographs; appearance and configuration follow each project's delivery.

At a glance

2.5MWSingle SST
800VDCDC bus
≥98.5%SST peak efficiency
≈2.3hBackup from 5.0 MWh

Overview

Power Block 2.0 is built around a solid-state transformer that converts medium-voltage AC to an 800 VDC bus with fewer intermediate stages. Current design documents use a 20 ft reference module.

One SST straight to 800 VDC, for Vera Rubin-class and later high-density AI clusters.

Power flow

  1. MV AC
  2. SST 2.5 MW
  3. 800 VDC bus
  4. Solid-state breakers
  5. Busway
  6. Racks

Whether rack-side conversion is needed depends on the selected rack's input; protection and conversion stages are never bypassed.

800 VDC is the high-voltage DC direction for next-generation AI factories. Whether a rack accepts 800 VDC directly depends on its version — the public DGX Vera Rubin NVL72 hardware guide, for example, describes 415–480 VAC input converted to 54 VDC inside the rack, so such racks need rack-side conversion.

Storage, racks, grid and monitoring

Grid
Medium-voltage connection designed to local grid codes and interconnection terms.
Storage
KABUTO ENERGY storage can be coupled as backup; DC- or AC-side coupling is decided per project.
Racks
Connected through DC distribution and protection, with rack-side conversion where required.
Monitoring
Power, storage and thermal status reported to one site monitoring layer.

Short-circuit protection, insulation monitoring, grounding scheme and isolation for the DC system are set at design stage from the load profile and local codes.

Tech specs

Electrical

Power unit Design value1 × SST 2.5 MW
Peak efficiency Design value≥ 98.5 %
Overload Design value120 % for 5 s; 150 % current-limited 150 ms
MV input Design valueJapan 6.6 kV · SE Asia/Australia 11 kV · Europe 20–22 kV
DC bus Design value800 VDC two-wire, main bus 4,000 A
Protection Design valueSolid-state breakers 2 × 1,600 A
Grounding Design valueMid-point high-resistance ±400 V + insulation monitoring

Backup & auxiliary

Storage backup Design valueKABUTO ENERGY 5.0 MWh + 2.5 MW bidirectional DC/DC, online hot standby, ~2.3 h
Auxiliary supply Design value800 VDC → 2 × 250 kVA grid-forming inverters for CDUs, pumps and dry coolers: cooling continues through outages

Standard unit

Standard unit Design valuePower 20 ft + compute 40 ft + thermal 40 ft + storage 20 ft
IT load Design valueGen A ≈ 1.74 MW (7 × Vera Rubin NVL72); Gen B ≤ 2.0 MW
Cooling Design valueSecondary 45 / 55 °C → primary 42 / 52 °C → dry coolers 4+1 × 600 kW, no water use
Scaling Design valueScale by replicating units; at 1 MW per rack, 2 racks per unit stay within 2.5 MW

Figures are scheme-stage design values, confirmed by project engineering and equipment-maker data. The Basis column separates source values, design values and items set per project; project items are fixed in the formal technical agreement.