KABUTO TECHNOLOGY
KABUTO AI · Panama power · 240 VDC

Power Block 1.0

Proven. Ready to build now.

KABUTO AI Power Block 1.0

Product renders, not photographs; appearance and configuration follow each project's delivery.

At a glance

2.5MWUnit capacity
240VDCDC bus
≤98.5%MV-to-DC efficiency
2.2MWDesign IT load per unit

Overview

Power Block 1.0 is built around a Panama power system that converts medium-voltage AC to a 240 VDC bus feeding compute racks. Current design documents use a 40 ft reference module.

Built entirely from series-production equipment, for existing racks and projects that must go live fast.

Power flow

  1. MV AC 10 kV
  2. Phase-shift transformer
  3. Rectifiers 4 × 625 kW
  4. 240 VDC bus A / B
  5. Row distribution
  6. Racks

Whether rack-side conversion is needed depends on the selected rack's input; protection and conversion stages are never bypassed.

Storage, racks, grid and monitoring

Grid
Medium-voltage connection designed to local grid codes and interconnection terms.
Storage
KABUTO ENERGY storage can be coupled as backup; DC- or AC-side coupling is decided per project.
Racks
Connected through DC distribution and protection, with rack-side conversion where required.
Monitoring
Power, storage and thermal status reported to one site monitoring layer.

Short-circuit protection, insulation monitoring, grounding scheme and isolation for the DC system are set at design stage from the load profile and local codes.

Tech specs

Electrical

MV input Design value10 kV dual feed, duty and standby (adapted to local grid)
Phase-shift transformer Design valueDry type, 2.5 MVA
Rectification Design value4 × 625 kW, 30 kW modules N+1, hot-swappable
Rated output Design value2.5 MW
DC bus Design value240 VDC, ~270 V operating (server input 192–288 V)
MV-to-DC efficiency Design value97.5–98.5 %
Redundancy Design valueModule N+1; 2N uses two sets

Backup & auxiliary

First-layer backup Design value240 V bus-connected lithium, ≥ 15 min at full load, no transfer
Auxiliary supply Design value10 / 0.4 kV 1,600 kVA dry transformer → 400 VAC; modular UPS 15 min
Second-layer backup Design valueKABUTO ENERGY 5.0 MWh + 2.5 MW grid-forming PCS, ~1.8–2 h at full load

Standard unit

Standard unit Design valuePower 40 ft + backup & aux 40 ft + compute 2 × 40 ft + thermal 40 ft + storage 20 ft
Unit footprint Design value44.4 × 18.4 m
Design IT load Design value2.2 MW
Annual PUE Design value~1.10 (summer peak ~1.15)

Figures are scheme-stage design values, confirmed by project engineering and equipment-maker data. The Basis column separates source values, design values and items set per project; project items are fixed in the formal technical agreement.