KABUTO TECHNOLOGY
KABUTO ENERGY · Utility storage

5.0 MWh

5 MWh per enclosure. The grid-scale workhorse.

KABUTO ENERGY 5.0 MWh

Product renders, not photographs; appearance and configuration follow each project's delivery.

At a glance

5,015.9kWhNominal energy
2,507.9kWMax charging power (0.5P)
≤3°CCell temperature spread
IP55Ingress protection

Overview

A 20 ft liquid-cooled enclosure holding 5,015.9 kWh, with three layers of protection from cell to system and ≤ 3 °C cell temperature spread.

Specifications from the November 2026 product brochure; fire-protection and certification items marked optional are confirmed per project.

Tech specs

Model: ESD1331-05P5015

Electrical

Cell DatasheetLFP 314 Ah
Nominal energy Datasheet5,015.9 kWh
Nominal voltage Datasheet1,331.2 V
Recommended voltage range Datasheet1,164.8–1,497.6 V
Max. charge/discharge rate Datasheet0.5P @ 25 °C
Max. charging power Datasheet2,507.9 kW (0.5P)

Environment

Storage temperature Datasheet−30 ~ 60 °C
Operating temperature Datasheet−30 ~ 55 °C
Humidity Datasheet≤ 95 %
Altitude Datasheet≤ 3,000 m

Structure

Dimensions (W × D × H) Datasheet6,058 × 2,438 × 2,896 mm
Weight Datasheet≈ 44 t
Ingress protection DatasheetIP55
Cooling DatasheetLiquid cooling
Communication DatasheetCAN, RS485, Ethernet · Modbus-TCP/IP, Modbus RTU, IEC 104

Fire protection

Fire suppression DatasheetExplosion-proof exhaust; temperature / smoke / combustible-gas detection; pack-level immersion (optional); aerosol; prefabricated sprinkler (optional)

Standards

China DatasheetGB/T 36276, GB/T 44240
US DatasheetUL 1642, UL 1973, UL 9540, UL 9540A, NFPA 69, NFPA 855, NFPA 68 (optional)
Europe DatasheetIEC 62619, IEC 62477-1, IEC 61000-6-2/-4, IEC 62933-5-2, IEC 60068-2, IEC 62620, IEC 61427-1/-2, IEC 60730, IEC 63056, EU 2023/1542, IEC 62933-2-1, IEC 62040-1
Australia / NZ DatasheetAS/NZS 3000:2008+A1+A2, AS/NZS 5139:2019, AS/NZS 3008.1.1/2
Shipping DatasheetUN38.3, UN3536

The Basis column separates source values, design values and items set per project; project items are fixed in the formal technical agreement.